Enter the number of conductors by gauge, devices such as switches and receptacles, whether grounding conductors and an internal cable clamp are present and the box volume in cubic inches marked in the box. Under the National Electrical Code, each conductor counts by volume, 2 cubic inches for 14 gauge, 2.25 for 12 gauge and 2.5 for 10 gauge, each device counts as two conductors of the largest size, all grounding conductors together count as one and internal clamps count as one. Count conductors that originate in the box.
Conductors that pass through uncut may count differently from those spliced or terminated, and fixtures and fittings add volume. Rules differ for different wire gauges mixed in a box. Box volume is stamped inside the box or given in the catalog.
Work should follow the adopted code and be done by a qualified person.
Required box volume (cu in) from #14 AWG conductors
| #14 AWG conductors | 4 |
|---|---|
| #12 AWG conductors | 0 |
| Devices (switches/receptacles) | 1 |
| Grounding conductors present | Yes |
| Internal cable clamp present | Yes |
| Box volume | 18 |
| Required box volume (cu in) | 16 |
| Percent of entered box volume used | 88.9% |
Common error: Counting only the conductors. Devices, clamps and grounds all take volume, and leaving them out puts too much in the box.
Electrical Box Fill: formula
Electrical Box Fill: changing #14 AWG conductors
| #14 AWG conductors | Required box volume (cu in) | Percent of entered box volume used |
|---|---|---|
| 2 | 12 | 66.7% |
| 3 | 14 | 77.8% |
| 4 (example) | 16 | 88.9% |
| 5 | 18 | 100.0% |
| 6 | 20 | 111.1% |
Electrical Box Fill: compare input ranges
| Input | Tested from | To | Required box volume (cu in): low input | Required box volume (cu in): high input | Swing |
|---|---|---|---|---|---|
| Devices (switches/receptacles) | 0 | 2 | 12 | 20 | 8 (50%) |
| #14 AWG conductors | 3 | 5 | 14 | 18 | 4 (25%) |
| #12 AWG conductors | 0 | 1 | 16 | 19.3 | 3.3 (20%) |
| Grounding conductors present | Yes | No | 16 | 14 | 2 (13%) |
| Internal cable clamp present | Yes | No | 16 | 14 | 2 (13%) |
| Box volume | 16 | 20 | 16 | 16 | 0 |
Electrical Box Fill: individual input comparisons
| Input | Value | Required box volume (cu in) | Percent of entered box volume used |
|---|---|---|---|
| #14 AWG conductors | 2 | 12 | 66.7% |
| 3 | 14 | 77.8% | |
| 4 | 16 | 88.9% | |
| 5 | 18 | 100.0% | |
| 6 | 20 | 111.1% | |
| #12 AWG conductors | 0 | 16 | 88.9% |
| 0 | 16 | 88.9% | |
| 0 | 16 | 88.9% | |
| 1 | 19.3 | 106.9% | |
| 2 | 21.5 | 119.4% | |
| Devices (switches/receptacles) | 0 | 12 | 66.7% |
| 0 | 12 | 66.7% | |
| 1 | 16 | 88.9% | |
| 2 | 20 | 111.1% | |
| 3 | 24 | 133.3% | |
| Grounding conductors present | Yes | 16 | 88.9% |
| No | 14 | 77.8% | |
| Internal cable clamp present | Yes | 16 | 88.9% |
| No | 14 | 77.8% | |
| Box volume | 14 | 16 | 114.3% |
| 16 | 16 | 100.0% | |
| 18 | 16 | 88.9% | |
| 20 | 16 | 80.0% | |
| 22 | 16 | 72.7% |
Required box volume (cu in): #14 AWG conductors against Devices (switches/receptacles)
| #14 AWG conductors / Devices (switches/receptacles) | 0 | 1 | 3 |
|---|---|---|---|
| 2 | 8 | 12 | 20 |
| 3 | 10 | 14 | 22 |
| 4 | 12 | 16 | 24 |
| 5 | 14 | 18 | 26 |
| 6 | 16 | 20 | 28 |
Electrical Box Fill: values and definitions
| Quantity and definition | Value used |
|---|---|
| #14 AWG conductors — Count of 14 AWG conductors entering the box. | 4 |
| #12 AWG conductors — Count of 12 AWG conductors entering the box. | 0 |
| Devices (switches/receptacles) — Number of switches or receptacles mounted in the box; each counts as two conductors. | 1 |
| Grounding conductors present — Whether any grounding conductors are present (they count together as one conductor). | Yes |
| Internal cable clamp present — Whether the box has an internal cable clamp (it counts as one conductor). | Yes |
| Box volume — Rated cubic-inch volume of the box. | 18 |
| Required box volume (cu in) | 16 |
| Percent of entered box volume used | 88.9% |
Devices (switches/receptacles): half and double
| Devices (switches/receptacles) | Required box volume (cu in) |
|---|---|
| 0.5 | 14 |
| 1 | 16 |
| 2 | 20 |
A box has a fixed volume, and the code counts how much room each conductor, device and clamp takes. In the example, four 14 gauge conductors at 2 cubic inches each give 8, a device counts as two allowances, or 4, and the ground and the internal clamp add 2 each, for 16 cubic inches required. An 18 cubic inch box is 88.9 percent used.
Crowding wires into a small box overheats them and makes them hard to install safely.
Read the volume marked inside the box and use the allowance for the largest conductor size present. Add for extra devices, fittings and any additional grounds.
See conduit capacity on the conduit fill calculator, wire ratings on the wire ampacity page and voltage loss on the voltage drop calculator. The cubic feet and rectangular prism pages relate to volumes, and the watts to amps calculator sizes circuits.
What if the box is too full?
Use a larger or deeper box, or an extension ring where allowed, since overfilled boxes are hazardous and violate code.