Voltage Drop Calculator

Estimate voltage drop and power loss over a wire run.

Excessive voltage drop wastes power and can undersize a circuit's effective capacity. At the worked-example inputs, the voltage drop is 4.8 volts. Voltage drop is the loss of voltage along a wire, caused by its resistance, and it also wastes power as heat. On the example, 15 amps over 100 feet of 12 AWG wire drops about 4.8 volts and loses about 71 watts, roughly 4% of a 120-volt supply. The National Electrical Code recommends keeping the drop within about 3% on a branch circuit and 5% overall for efficient operation. Use larger wire for long runs to reduce it. It returns voltage drop (volts), power lost (watts).

FreeNo sign-upInputs stay in-browserCSV exportReviewed August 28, 2026
LAST REVIEWEDAugust 28, 2026Inputs stay in your browser
Live calculation

Enter your numbers

Calculated result
Voltage drop (volts)4.8
Power lost (watts)71.5
Sensitivity check

What if current (amps) changes?

-10% input4.3
0% input4.8
+10% input5.2

Transparent method

The formula

Voltage drop = current × (resistance per 1000ft ÷ 1000) × distance × 2 (round trip)

Worked example

Voltage drop (volts)4.8
Power lost (watts)71.5

Example inputs

Current (amps)15
One-way distance (ft)100
Wire gauge12 AWG

How to interpret the result

Voltage drop wastes power as heat along the wire itself and can quietly undersize a circuit's real capacity, because a device at the far end of a long run receives less voltage than what left the source. A run long enough or thin enough can leave a device technically underpowered even though the breaker and source voltage both look completely fine.

Before you rely on it

What to check

Check the calculated drop against the wire run's actual length and gauge, not just the rated capacity of the breaker or source, since a long run is where the real loss accumulates.

The common error

Where people go wrong with voltage drop calculator

Sizing a wire run by the connected load alone without checking voltage drop over distance. A wire rated fine for the load at the source can still deliver meaningfully reduced voltage at the far end of a long run.

Sensitivity evidence

How current (amps) changes the voltage drop (volts)

Voltage Drop Calculator: voltage drop (volts) and power lost (watts) across a range of current (amps), every other input held at the worked-example value.
Current (amps)Voltage drop (volts)Power lost (watts)
123.845.7
144.462.2
15worked example4.871.5
175.491.8
185.7102.9

Every input, tested

Which input moves the voltage drop (volts) most

Voltage Drop Calculator: voltage drop (volts) with each input moved on its own, every other input held at the worked-example value.
InputTested fromToVoltage drop (volts) at each endSwing
Wire gauge14 AWG6 AWG7.6 to 1.26.4 (134%)
One-way distance (ft)901104.3 to 5.20.953 (20%)
Current (amps)14174.4 to 5.40.953 (20%)

Two variables at once

Voltage drop (volts) by current (amps) and one-way distance (ft)

Voltage Drop Calculator: voltage drop (volts) at each combination of current (amps) (rows) and one-way distance (ft) (columns).
Current (amps) \ One-way distance (ft)80100120
1233.84.6
143.64.45.3
153.84.85.7
174.35.46.5
184.65.76.9

Step by step

The worked example, input by input

Worked-example inputs and the results they produce for the voltage drop calculator.
InputValue usedWhat it means
Current (amps)15
One-way distance (ft)100
Wire gauge12 AWGThinner wire (higher AWG number) has more resistance per foot.
Voltage drop (volts)4.8
Power lost (watts)71.5

Inputs, definitions and assumptions

Current (amps)

One-way distance (ft)

Wire gauge

Thinner wire (higher AWG number) has more resistance per foot.

Where the inputs come from

Enter the current in amps, the one-way length of the wire run in feet and the wire gauge, which sets the resistance per 1,000 feet: about 1.59 ohms for 12 AWG copper, 2.53 for 14 AWG and 0.98 for 10 AWG. Measure the wire path, not the straight-line distance. The tool doubles the distance for the round trip. Use the actual expected current, not the breaker rating, for a realistic drop.

When the result stops applying

Resistance rises with temperature, and aluminum wire has higher resistance than copper. AC circuits with inductive loads add impedance. The tool covers single-phase two-wire runs. Motors starting draw more than their running current, so the momentary drop is larger. Electrical work should follow local code and be done by a qualified person.

What to compare it with

Relate power to current on the watts to amps calculator, see Ohm's law and power on the Ohm's law page, and combine resistors on the resistor calculator. The LED resistor and voltage divider pages handle low-voltage electronics, and the energy and power converters change units.

People also ask

Frequently asked questions

How much voltage drop is acceptable?

Generally no more than 3% on a branch circuit and 5% total for feeder and branch together, to keep equipment running efficiently.

How can I reduce voltage drop?

Use a thicker wire, shorten the run, lower the current or raise the supply voltage, since each of these reduces the loss along the wire.

Why is the distance doubled?

Current flows out and back through the circuit, so the resistance is that of twice the one-way length.