Voltage Drop Calculator

The selected 12-AWG copper scenario uses 1.588 Ω per 1,000 ft. For 100 ft one-way, the two-wire loop is 200 ft; loop resistance is 0.3176 Ω. At 15 A, drop is 4.764 V and resistive loss is 71.46 W.

On a 120 V source that drop is 3.97%. The calculation does not establish conductor ampacity or code compliance.

Voltage Drop Calculator: inputs

Calculated result
Voltage drop (volts)4.8
Power lost (watts)71.5

Voltage Drop Calculator: Current (amps) sensitivity

Voltage Drop Calculator: Current (amps) and Voltage drop (volts)5 calculations vary the “Current (amps)” input while holding the other entered inputs constant.123.8144.4154.8175.4185.7

Voltage Drop: formula

Voltage drop = current × (resistance per 1000ft ÷ 1000) × distance × 2 (round trip)

NIST Physical Measurement Laboratory · NBS Handbook 100: Copper wire tables

Enter the current in amps, the one-way length of the wire run in feet and the wire gauge, which sets the resistance per 1,000 feet: about 1.59 ohms for 12 AWG copper, 2.53 for 14 AWG and 0.98 for 10 AWG. Measure the wire path, not the straight-line distance. The tool doubles the distance for the round trip.

Use the actual expected current, not the breaker rating, for a realistic drop.

Voltage Drop: worked example

Current (amps)15
One-way distance (ft)100
Wire gauge12 AWG
Voltage drop (volts)4.8
Power lost (watts)71.5

Resistance rises with temperature, and aluminum wire has higher resistance than copper. AC circuits with inductive loads add impedance. The tool covers single-phase two-wire runs.

Motors starting draw more than their running current, so the momentary drop is larger. Electrical work should follow local code and be done by a qualified person.

Voltage Drop: changing Current (amps)

Current (amps)Voltage drop (volts)Power lost (watts)
123.845.7
144.462.2
15 (example)4.871.5
175.491.8
185.7102.9

Voltage Drop: compare input ranges

InputTested fromToVoltage drop (volts): low inputVoltage drop (volts): high inputSwing
Wire gauge14 AWG6 AWG7.61.26.4 (134%)
One-way distance (ft)901104.35.20.953 (20%)
Current (amps)14174.45.40.953 (20%)

Voltage Drop: individual input comparisons

InputValueVoltage drop (volts)Power lost (watts)
Current (amps)123.845.7
144.462.2
154.871.5
175.491.8
185.7102.9
One-way distance (ft)803.857.2
904.364.3
1004.871.5
1105.278.6
1205.785.8
Wire gauge14 AWG7.6113.6
12 AWG4.871.5
10 AWG345
8 AWG1.928.3
6 AWG1.217.8

Voltage Drop: combined input changes

Current (amps) / One-way distance (ft)80100120
1233.84.6
143.64.45.3
153.84.85.7
174.35.46.5
184.65.76.9

Voltage Drop: which assumptions move the result?

Voltage Drop: Voltage drop (volts) as Wire gauge changesVoltage drop (volts) starts at 7.6. Moving Wire gauge from 14 AWG to 6 AWG changes it to 1.2, with Current (amps) 15; One-way distance (ft) 100 kept fixed.14 AWG7.612 AWG4.810 AWG38 AWG1.96 AWG1.2
Chart quantityDisplayed settings
Wire gauge14 AWG → 6 AWG
Voltage drop (volts)7.6 → 1.2
Current (amps)15
One-way distance (ft)100
Voltage Drop: Voltage drop (volts) as One-way distance (ft) changesVoltage drop (volts) starts at 3.8. Moving One-way distance (ft) from 80 to 120 changes it to 5.7, with Current (amps) 15; Wire gauge 12 AWG kept fixed.803.8904.31004.81105.21205.7
Chart quantityDisplayed settings
One-way distance (ft)80 → 120
Voltage drop (volts)3.8 → 5.7
Current (amps)15
Wire gauge12 AWG

Voltage Drop: values and definitions

Quantity and definitionValue used
Current (amps)15
One-way distance (ft)100
Wire gauge — Thinner wire (higher AWG number) has more resistance per foot.12 AWG
Voltage drop (volts)4.8
Power lost (watts)71.5

Common error: Sizing a wire run by the connected load alone without checking voltage drop over distance. A wire rated fine for the load at the source can still deliver meaningfully reduced voltage at the far end of a long run.

Science & Electronics calculators: Dilution Calculator, pH Value Calculator, Half-Life Calculator, Series and Parallel Resistor Calculator, LED Resistor Calculator, Watts to Amps Calculator.

Voltage drop wastes power as heat along the wire itself and can quietly undersize a circuit's real capacity, because a device at the far end of a long run receives less voltage than what left the source. A run long enough or thin enough can leave a device technically underpowered even though the breaker and source voltage both look completely fine.

Check the calculated drop against the wire run's actual length and gauge, not just the rated capacity of the breaker or source, since a long run is where the real loss accumulates.

Relate power to current on the watts to amps calculator, see Ohm's law and power on the Ohm's law page, and combine resistors on the resistor calculator. The LED resistor and voltage divider pages handle low-voltage electronics, and the energy and power converters change units.

Does the voltage-drop result size a safe circuit?

No. Voltage drop describes one electrical effect. Ampacity, temperature ratings, installation conditions, overcurrent protection and the applicable electrical rules require a separate circuit-design check.

Why is one-way distance doubled?

The assumed two-conductor circuit includes an outgoing and return path. A different circuit topology requires a different impedance model.

Does higher supply voltage alone reduce wire loss?

Not at fixed current and resistance: I²R stays the same. For the same delivered power, a higher voltage can allow lower current and thereby reduce loss.